Support LBS control in sync;
Have the function of fan speeding control with intelligence;
Comprehensive electrical isolation protection and bypass
protection;
Support bypass maintenance (three phase inlet and single phase
outlet/three phase inlet and three phase outlet);
Large LCD Chinese/English display interface, user friendly;
Make automatic alarm, self-detection, find problems easily in time
come true;
Three - stage extended charge design to ensure superior battery
performance;
Only online UPS, and output high quality sine wave power that
provide the user a better power supply protection;
Wider range of input voltage that working under large fluctuations
grid environment, can be in commercial power mode without switching
to battery mode, which can protect the battery lifespan.
Design:
1. Long-term power supply design
2. Zero transition time
3. Can be used with large motor
4. Input power factor correction
5. Configure smart slot
6. DC Start
7. Configure standard battery module
8. Auto restart function
Technical data
| Model | X1-1101(L) | X1-1102(L) | X1-1103(L) | X1-1106L | X1-1110L |
| Capadity | 1KVA /0.8KW | 2KVA /1.6KW | 3KVA / 2.4KW | 6KVA / 4.8KW | 10KVA / 8KW |
| Input |
| Connection Mode | Single Phase + Ground |
| Input Voltage | 200 / 208 / 220 / 230 /240VAC |
| Voltage Range | 110-300VAC |
| Frequency | 40-70Hz |
| Power factor | ≥0.99 |
| Output |
| Output Voltage | 200 / 208 / 220 / 230 /240VAC |
| Voltage regulation | ±1% |
| Frequency | S y n c h r o n o u s correction range | 46-54Hz / 56-64Hz |
| Battery Model | 50Hz ±0.1Hz / 60Hz ±0.1Hz |
| Distortion(THDU) | ≤3% |
| Peak Cofficient | ≥3:1 |
| Overload Capacity | 110%,convey to bypass after 1h;125%,convey to bypass after
10min;150%,convey to bypass after 1min. |
| Time switching | Electric City/Battery | 0ms |
| Inverter/Bypass | <4ms (standard environment) | 0ms |
| Battery |
| Standard Machine | Battery Cells | 2 | 4 | 6 | / |
| Charging Current | 1.0A (MAX) | / |
| Battery Model | 12V / 9Ah | / |
| Long Lasting | Battery Cells | 3 | 6 | 8 | 16(16-20 optional) |
| Charging Current | 1A/2A/4A/6A settable |
| Battery Model | Depends on the applicant |
| Control Management |
| City Electricity Model | ≥91% | ≥93% |
| Battery Model | ≥91% | ≥93% |
| Display Interface |
| LCD/LED | Loading Size, Battery Capacity, City Electricity Mode, Battery
Mode, Bypass Mode, Fault Indication |
| Control Management |
| Intelligent RS-232/USB | Support Windows 2000/2003/XP/Vista/2008,Windows 7/8,Linux,Unix and
MAC |
| Option SNMP | Support SNMP Internet Management |
| Environment |
| Temperature | 0-40℃ |
| Relative Humidity | 0-95%(Non Condensing) |
| Noise | < 50dB @1m | < 55dB @1m | < 58dB @1m |
| Physical Character |
Standard Machine | Size: Width*Depth *Height(mm) | 438*310*88 | 438*410*88 | 438*630*88 | / | / |
| Net Weight(kg) | 12 | 18 | 29 | / | / |
| L o n g Lasting | Size:Width*Depth *Height(mm) | 438*310*88 | 438*410*88 | 438*530*88 | 438*580*133 |
| Net Weight(kg) | 5 | 7 | 8 | 12 | 16 |